Originally Posted by 60ApacheC20
Plus there is the expense of running new electrical and plumbing the unit. These pigs require a 50 amp circuit, dedicated wiring, the AC wire is even expensive.

If you're referring to the new compressor needing 50 amp circuit, that partly correct...it will need a 50 amp breaker to handle the inrush current, but the branch circuit wiring only needs to be #10 copper wire (the 5 hp motor only draws about 20 amps when running).